School Double Doors Stopped Closing After an AC Change: LCN 4040XP Door Closers, Aventura

School Double Doors Stopped Closing After an AC Change: LCN 4040XP Door Closers, Aventura

A school in Aventura emailed me about three sets of double doors that wouldn’t close all the way. The doors had been fine until the AC was modified, and the extra air pressure was holding them open. I replaced all six closers with LCN 4040XP units, set them to 8.5 lbs of opening force, and the doors close every time.

What the email said

They wrote, “Hey, we have an issue with 3 double doors that won’t close all the way. When can you guys come out and do some adjustment on these doors?”

I scheduled it for the end of that same day, because a school can’t leave its doors open overnight. I got there at 3 p.m., after the kids finished school.

What I found

I watched how each door swung. In the last 15 degrees, the closer couldn’t push the door shut. When I put my hand in the small gap, I could feel the air from the AC pushing against the door.

I tried making the closer spring stronger and adjusting it, but all six doors acted the same. That told me the closers weren’t strong enough to close the doors against the pressure.

Ruling out the hinges and the frame

I checked the hinges, then turned off the AC, and the door closed right away. A door that won’t close can point to a hinge or frame issue, but not here, because six doors stopped self closing at the same time. In large rooms, it’s very common for the AC to push too much air into the room.

So I asked the facility manager if they had recently changed the AC pressure. The answer was, “You know what, you’re right. The issue started the day after the AC was modified.”

Choosing the closers

We both agreed on a stronger closer with higher tension, and for this kind of application the LCN 4040XP is the winner. I replaced all six closers on the three double doors and set each one at the door with a gauge to 8.5 lbs of opening force, the figure Florida uses for exterior doors. That’s strong enough to close and latch against the air pressure, and light enough for a student to open.

I also explained to the school what had changed, so they know a future AC adjustment can affect the doors again.

The work

The job took three and a half hours, including the assessment, removing the old closers, installing and adjusting the new ones, and cleaning up. We always leave the site clean after an installation.

Before I left, the facility manager walked all the exterior doors with me to check that they were self closing properly. Besides these three double doors, everything was in great condition.

What was on the invoice

Only the six new LCN closers and the installation. My pricing is upfront, and you approve it before I start.

What a real locksmith knows

I tell customers that every door is different, and we need to fit the best product for each application. When there’s an air pressure issue, I always go with the bigger LCN model, so it lasts a long time and has the strength to force the door closed against the pressure. I also check the door frame and the door alignment, because they can cause the same problem.

The local angle

Aventura is in Miami-Dade. Large rooms like the ones in this school get a lot of air from the AC, and when that pressure changes, it shows up first at the exterior doors.

Exterior door not closing all the way since the AC was changed? Call Around The Lock at (954) 371-5674.

From the Job

On-Site Photos

School Double Doors Stopped Closing After an AC Change: LCN 4040XP Door Closers, Aventura photo 1
School Double Doors Stopped Closing After an AC Change: LCN 4040XP Door Closers, Aventura photo 2
School Double Doors Stopped Closing After an AC Change: LCN 4040XP Door Closers, Aventura photo 3
School Double Doors Stopped Closing After an AC Change: LCN 4040XP Door Closers, Aventura photo 4
FAQ

Common Questions

Why did my doors stop closing after AC work?

At an Aventura school, the AC change pushed more air into the building, and in the last 15 degrees the closers couldn't push the doors shut against it. When I turned off the AC, the door closed right away. The facility manager confirmed the problem started the day after the AC was modified, so I replaced the closers with stronger ones.

What door closer do you use when air pressure keeps a door from closing?

When there's an air pressure issue, I always go with the bigger LCN model. On this school job I installed LCN 4040XP closers on all three double doors, six closers in total. It has the strength to force the door closed against the pressure, and it's built to last a long time on a busy door.

How much force should an exterior door take to open?

Florida uses 8.5 lbs for exterior hinged doors. On the Aventura school doors, I set each new closer at the door with a gauge until it hit 8.5 lbs. That's strong enough to close and latch against the air pressure, and light enough that a student can still open the door.

Can a door closer be adjusted instead of replaced?

Sometimes. On this job I tried making the closer spring stronger and adjusting it first. All six doors still acted the same, which told me the closers weren't strong enough for the job anymore. That's when replacing them with a stronger LCN closer was the right call instead of more adjusting.

Could my door not closing be a hinge or frame problem?

It can be. I always check the hinges, the door frame, and the door alignment, because they can cause the same problem. At the Aventura school it wasn't the hinges or the frame: six doors stopped self closing at the same time, and the door closed right away when I turned off the AC.

How long does it take to replace door closers?

Six closers on three double doors took me three and a half hours. That included the assessment, removing the old closers, installing and adjusting the new ones, and cleaning the site. We always leave the site clean after an installation. I also walked the other exterior doors with the facility manager before I left.

More Services

Related Services

Door Hardware Installation

New deadbolts, knobs, levers, or smart locks. We install door hardware correctly the first time.

Learn more about Door Hardware Installation

Emergency Locksmith

Locked out? Our bonded & insured 24/7 mobile locksmiths reach you fast: homes, cars, businesses. Upfront pricing, no surprises.

Learn more about Emergency Locksmith

Lock Change & Rekey

Moving in, lost a key, or want to upgrade your security? We rekey or replace your locks fast and affordably.

Learn more about Lock Change & Rekey

Car Key Replacement

Lost your car key or need a spare? We cut and program replacement keys for most makes and models on the spot.

Learn more about Car Key Replacement
Recent Work

More Recent Jobs

Medeco High Security Commercial Lock Change: Maxum Deadbolt and Keyed-Alike Cylinders, Dania Beach
Dania Beach

Medeco High Security Commercial Lock Change: Maxum Deadbolt and Keyed-Alike Cylinders, Dania Beach

Commercial locksmith in Dania Beach: I changed 3 doors to Medeco high security locks, keyed alike, in 2 hours of labor. (954) 371-5674.

Read more →
Contractor Lost a Key to the House: European Cylinder Rekey in Fort Lauderdale
Fort Lauderdale

Contractor Lost a Key to the House: European Cylinder Rekey in Fort Lauderdale

Lost contractor key to your house? I rekeyed all 6 locks at a Fort Lauderdale home instead of replacing them. Call (954) 371-5674.

Read more →
A Step at a Sunrise Stockroom Door Was Blocking Dollies and Carts
Sunrise

A Step at a Sunrise Stockroom Door Was Blocking Dollies and Carts

A stockroom back door at a Sunrise facility had a step that blocked dollies and carts. We installed a threshold ramp matched to the door jamb height, so employees now push straight through without stopping.

Read more →